Zerio-Plus EDA-Z5020 Manual de instrucciones Pagina 5

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 48
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 4
INSTRUCTION MANUAL - Issue 1 - 07/2014 | 5
CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
The Zerio Plus system has been approved by Intertek to meet EN54 parts 2 and 4. The panels were tested and
approved in their default con guration. This manual lists all available panel options and settings, some of which
can be set in a way that would result in a system that does not comply with EN54. The EN54 approved settings are
listed below:
Setup Type: Standard
Test Mode Type: By Zone
Test Mode Timeout: 0
Relay 1: Fire Routing Relay
Relay 2: Fault Relay safe
Relay 3: Sounder circuit
Relay 4: Sounder circuit
Relays: FIRE & SOUNDERS ON
Panel Buzzer: Enabled
Code Protect: ON
Device Verify Time: 390 seconds or less
Sounder Tone: Swept
Input Type: Latching
Input Relay Options: Relays O
Fire & Sounders On
Heat Detector Type: A1S
Fault Relay: Enabled
Device Faults: Enabled
Panel Faults: Enabled
1.0 - EN54 APPROVED CONFIGURATION
Vista de pagina 4
1 2 3 4 5 6 7 8 9 10 ... 47 48

Comentarios a estos manuales

Sin comentarios