4. Advanced User Operations
4.1 General
Assuming the correct password is entered, the user can sign on as an advanced user. This allows some extra functions not available to the
basic user. Only people who have been trained in the operation of the system should be allowed access at this level as certain operations
of the fire alarm can be disabled (although they will be automatically enabled after a short timeout period)
4.2 View Access Codes – Advanced, Service and Commissioning users only.
The access code / password is a 4 digit number with each digit in the range of 1 to 4. To view the current passwords press the ‘MENU’
button and enter the correct password for an ‘Advanced User’. The default is 2222. Using the cursor keys, select ‘1-Setup’, select ‘2-
Access Codes’ and select ‘1-View Codes’. A screen, as shown below, will list the passwords for the basic user labelled ‘AL1’ and the
advanced user labelled ‘AL2’. Access codes for other users (Service or Commissioning) can only be viewed if entering the menu system
as one of those users.
AL1 1111 AL2 2222
CANCEL to exit
4.3 Changing Access Codes – Advanced, Service and Commissioning users only.
An advanced user can change the password for the basic and advanced user. The password is a 4 digit number with each digit ranging
from 1 to 4. To change the password, press the ‘MENU’ button, select ‘1-Setup’, select ‘2-Access Codes’ and select ‘2-Change Codes.
Using the cursor keys, select either the ‘advanced user’ (Access Level 2) or the ‘basic user’ (Access Level 1). Once selected, press
key to continue. Using the numbered keys enter the current password. Assuming this matches the stored user code you will
be prompted to enter the new password and then re-enter the new password to confirm. Press ‘ENTER’ to save the new password, or
cancel to exit without saving. A message will be displayed indicating that the password is being saved to the SIM and flash memory. At
each stage, the process can be aborted by pressing and holding the ‘CANCEL’ key.
Access Level 1 Enter Current Code Enter New Code Confirm New Code
Basic Use ---- ---- ----
Use keys Hold CANCEL to exit Hold CANCEL to exit Hold CANCEL to exit
Please note: No operator serviceable parts are contained within this panel. Always refer to a qualified technician