EDA-Z5008 & Z5020 - Installation and Operation Manual
Electro-Detectors Page 12
4.4 Select Test Mode – Advanced, Service and Commissioning users only.
BS5839 and EN54 specify what tests should be performed, and at what intervals. ALWAYS FOLLOW ANY TESTING SCHEDULE
OR ROUTINE RECOMMENDED BY THE SYSTEM INSTALLER. As a rough guide the system should be tested weekly, but sounders
only need to be tested every month.
Test mode allows a system to be tested with minimal disruption to the occupants of a building. This is achieved by putting into Test
Mode, any zone(s) in which a device to be tested is located, which normally disables output devices and/or sounders from operating
should an alarm occur within the Test Mode zone(s).
Either a zone or group of zones can be selected to be tested. Should anything happen outside of these selected zones the system will
operate as normal and the sounders will sound. If the whole system is to be tested or the system wants to be soak tested then all zones can
be isolated by using the ‘ALL’ setting.
Test Mode is activated at the end of a sequence of instructions given on the screen to set various Test Mode parameters. Once selected,
the option is also given to save the parameters so that they can be used for subsequent test mode operations. Note that Advanced, Service
and Commissioning users each have their own set of parameters stored individually.
Note: whilst in Test Mode the Sound Alarm panel button will still operate as usual.
To select Test Mode, press ‘MENU’, and enter a valid password. Select ‘4-Test Mode’ then select ‘1-Enable Test’.
Zones – Advanced, Service and Commissioning users only
The system now requires that each zone to be operated in Test Mode is selected. Scroll to the appropriate zone number using the or
keys, and press the ‘ENTER’ key to select that zone. A ‘*’ will be indicated next to the zone number on the display. Use the or keys
to select any other zones containing devices that are to be tested at the same time, pressing ‘ENTER’ key to select to select each zone in
turn. If a zone is selected in error, it can be de-selected for test mode by using the or keys to scroll to that zone, and pressing
‘ENTER’ again. The ‘*’ indicator next to the zone on the display will extinguish to show that the zone is no longer selected for test mode.
If you want to test all zones then position the cursor by ‘All’ and press ‘Enter’. A’*’ indicator will be displayed.
Failure to select all the required zone(s) will mean the system will operate as normally for those zones – a device alarm within the zone
will set an alarm in that zone.
Having selected the required zone(s), use the ‘’ key to continue.
Zone 05 Zone 05 *
ENTER to select Use keys
Sounders – Advanced, Service and Commissioning users only
If sounders within the zone are to be disabled, set ‘Sounders’ to OFF. If sounders are required to operate in test mode, set the parameter to
ON.
Sounders OFF
ENTER to continue
Tone Commissioning users only
. Not implemented on early versions of the system.
If sounders are set to ON, they can be set for SHORT or FULL operation. A setting of SHORT causes any activated sounders to silence
automatically after 6 seconds. The FULL option causes continual sounding until silenced at the panel. If using the short test tone, 60
seconds must be left after the sounders have silenced before testing further devices.
Actuators– Advanced, Service and Commissioning users only
If actuators are not required to operate then set ‘Actuators’ to OFF. Actuators are output devices used to control equipment like magnetic
doors, other alarm systems, gas valve shut-offs, air conditioning etc. It would be normal for actuators to be isolated in an alarm test.
Beacons – Commissioning user only.
Not implemented on early versions of the system.
If beacons are not required to operate then set ‘Beacons’ to OFF.